OxyReduct® - Frequently Asked Questions
Q. What is the main advantage of the system?
A. It is impossible to have a fire.
Q. How long has the system been available?
A. The system has been available since 1999.
There are now over 40 OxyReduct® installations across
Europe used by recognised organisations such as BASF
Chemicals, Siemens and Hugo Boss.
Q. Can people enter the area?
A. At Oxygen levels of 15.0% people may
inhabit the area for up to 6 hours after which they
should take a 30-minute break
Q. H & S procedures?
A. The United Kingdom HSE has deemed that
an area with reduced oxygen content would be classed
as a confined working space. This means that there
should be a safe system of work and effective management
procedure in place that monitors the movement of people
through the area.
Q. How big is the equipment?
A. Equipment size is not dependent on
the volume of the room but on the leakage rate.
A space saving is realised when compared to extinguishing
systems, especially with larger volumes (> 500.0m3)
Q. How well does the room need to be sealed?
A. As well as possible. A better-sealed
room means smaller equipment and lower running costs.
An N50 value of less than 1.0 is ideal.
Q. How does HVAC effect system?
A. Re-circulation systems have no effect
on OxyReduct®.
Q. Do I still need fire detection?
A. Pyrolosis can still occur so high
sensitivity smoke detection should be employed to
indicate a technical problem in the area.
Q. What happens if power fails?
A. Nothing immediately, the control unit
is battery backed. Room protection depends on the
leakage rate.
Q. Are there any waste products generated?
A. The compressor creates a small amount
of water as part of its dehumidifying process. The
Nitrogen generator vents air with an enriched oxygen
(30.0%) content.
Q. Does the Compressor/Generator need to be in the room?
A. The Nitrogen generator must be within
30.0m of the compressor but there is no limit, within
reason, to how far the generator can be from the
risk area.
Q. What type of piping is required?
A. The nitrogen supply should be steel
until it enters the risk area. From then on the
pipe can be plastic. The pressure at the outlet in
the room is negligible.
Q. What power is required?
A. A 3-phase supply is required for the
compressor. The nitrogen generator and control unit
require a 240V supply.
Q. Does the system carry any approvals?
A. The system is being VdS approved
(expected mid 2003). Many pan-European insurance
companies have evaluated the fire prevention
performance and are writing risks only if protected by OxyReduct®.
Q. What maintenance is required?
A. The same maintenance interval as with
a fire alarm system. An air filter requires changing
annually. The Nitrogen Generator membrane has a life
of at least 10 years. |